Italy
CSRD sustainability reporting (ESRS E1 held and quoted) and the recast Energy Performance of Buildings Directive (held and quoted), with the Energy Efficiency Directive's energy audit duty named only.
How the register reads a supply point here
| Code and aliases | IT: rome, milan |
|---|---|
| Scheme | CSRD sustainability reporting (ESRS E1 held and quoted) and the recast Energy Performance of Buildings Directive (held and quoted), with the Energy Efficiency Directive's energy audit duty named only. Mandatory for operators of some size: a line here with no reporting owner raises the finding. |
| Text quoted | The CSRD (Directive (EU) 2022/2464) and ESRS text is held and quoted on the lines in this country: CSRD E1-CC, CSRD E1-GHG, EPBD Art. 9, EPBD Art. 13, EPBD Art. 14, EPBD Art. 16, EPBD Art. 19, 20, 21, 22, EPBD Art. 23, 24. |
| Demand response | Programme named: national demand response and flexibility markets run through the transmission operator and aggregators. A line here reads can take part where the meter, the class and the tariff allow. |
Requirement text quoted from the standards themselves, published at compliance.theartofservice.com, the same publisher as this register, read against the held text of each standard: our statement of each clause, not the instrument verbatim.
CSRD E1-CC Climate change (transition plan and targets)Disclose climate-change mitigation and adaptation, including a transition plan compatible with limiting warming to 1.5 C, climate targets, and the financial effects of climate-related risks and opportunities.
Common gap: No transition plan where E1 is material
Framework page: CSRD (Directive (EU) 2022/2464) and ESRS
CSRD E1-GHG GHG emissions (Scope 1, 2 and 3)Disclose gross Scope 1, Scope 2 (location- and market-based) and Scope 3 greenhouse gas emissions, total GHG emissions, and the methodologies and boundaries used, consistent with the GHG Protocol.
Common gap: Scope 3 omitted where material
Framework page: CSRD (Directive (EU) 2022/2464) and ESRS
EPBD Art. 9 Minimum Energy Performance Standards for non-residential and trajectories for residential (Article 9)Article 9 introduces MEPS for non-residential buildings: Member States establish maximum energy-performance thresholds, with the existing non-residential stock above the 16% worst performing buildings to be brought below that threshold by 2030, and the 26% worst-performing threshold by 2033. Article 9(3) requires Member States to set national trajectories fo...
Common gap: Non-residential portfolio with assets in the worst-performing 16% lacking a 2030 plan
Framework page: EPBD recast (Directive (EU) 2024/1275)
EPBD Art. 13 Technical building systems (Article 13)Article 13 requires Member States to set system requirements in relation to the overall energy performance, the proper installation, and the appropriate dimensioning, adjustment and control of the technical building systems (TBS) installed in existing buildings, namely heating, hot water, cooling, ventilation, large built-in lighting, building automation and...
Common gap: Eligible non-residential building above 290 kW HVAC output without BACS by 31 Dec 2024
Framework page: EPBD recast (Directive (EU) 2024/1275)
EPBD Art. 14 Infrastructure for sustainable mobility (Article 14)Article 14 requires Member States to ensure the installation of electric-vehicle (EV) recharging points and bicycle parking spaces in non-residential and residential buildings. Non-residential: new and major renovation with more than 5 car parking spaces: at least 1 recharging point per 5 spaces + bicycle parking; existing non-residential with more than 20 c...
Common gap: New building over 5 non-residential parking spaces without EV recharging point
Framework page: EPBD recast (Directive (EU) 2024/1275)
EPBD Art. 16 Data exchange (Article 16)Article 16 requires Member States to ensure that building owners, tenants and managers can have direct access to their building data via a single secure access point, including data from the technical building systems (Article 13), the EPC databases (Article 22), the renovation passport (Article 12) and any related metering / sub-metering data. Data sharing ...
Common gap: TBS data locked behind proprietary interfaces without owner / tenant / manager access
Framework page: EPBD recast (Directive (EU) 2024/1275)
EPBD Art. 19, 20, 21, 22 Energy Performance Certificates (Articles 19-22)Article 19 requires the issue of EPCs in defined cases: construction, sale, new lease (Article 19), with the EPC class shown in property advertisements. Article 19(7) requires Member States to introduce, by 29 May 2026, an A+++ to G scale (where A+++ corresponds to ZEB; A to NZEB; G is the worst performing 15% of national stock). Article 20 governs the issue...
Common gap: Sale or new lease without a valid EPC
Framework page: EPBD recast (Directive (EU) 2024/1275)
EPBD Art. 23, 24 Inspections of heating, ventilation and air-conditioning systems (Articles 23-24)Article 23 requires regular inspections of accessible parts of HVAC systems above defined kW thresholds (heating + combined heating-and-ventilation above 70 kW; air-conditioning + combined air-conditioning-and-ventilation above 70 kW). Inspection covers the efficiency and dimensioning of the system. Article 24 requires inspection reports made available to th...
Common gap: HVAC system above 70 kW lacking inspection records on schedule
Framework page: EPBD recast (Directive (EU) 2024/1275)
Register the supply points in Italy
Paste the list with the country on each line; every line here carries the scheme, the programme reading and, where the text is held, the clause. Eight supply points free, no account.
Build my energy register